How to set trigger (analog input) ? (Session based interface)
Mostrar comentarios más antiguos
Hi everyone
I would like to add a trigger using an analog input as a reference channel. I'm using the session based interface and a NI PXIe device.
How can I make it? I've already read the example but it's for an external trigger using a switch.
Thank you for your answers.
GD
Respuestas (1)
Nidhi Jain
el 15 de Jul. de 2014
Hi,
Have you tried doing:
>>s=daq.createSession('ni');
>>addAnalogInputChannel(s,'PXI1Slot2','ai0','RTD');
>>addAnalogInputChannel(s,'PXI1Slot3','ai1','RTD');
>>tc=addTriggerConnection(s,'PXI1Slot2/PXI_Trig1','PXI1Slot3/PXI_Trig0','StartTrigger');
As long as you have mentioned the source and destination correctly, the trigger does not need to be external. You can refer the doc for more information:
2 comentarios
Deroissart
el 15 de Jul. de 2014
Nidhi Jain
el 15 de Jul. de 2014
Hi,
When adding the trigger, the source and destination cannot be the same device so I think it won’t work if the same slot is mentioned for both source and destination.
The triggers PXi_Trig1 and PXI_Trig0 are digital triggers because the device I am using NI PXIe-4357 does not support analog triggers.
It looks like your device also supports only digital triggers so I think you won’t be able to add an analog trigger.