Why I get Nan values in when i connect an inverter into a 11kV grid feeder?

5 visualizaciones (últimos 30 días)
Eleni T
Eleni T el 21 de Sept. de 2023
Respondida: Sayan el 25 de Sept. de 2023
Hello.
I have a simulink model with a power grid with 3 feeders in 11kV. In each feeder i have connected several load profiles and everything is working. When i try to connect a PV inverter on the feeder, i get 'Nan' at the output of the inverter (e.g., for voltage, active and reactive power etc). The inverter is connected through a transformer 11lV to 400V and a filter.
Something weird is that when i connect the inverter close to the source ( between the source and a load), i don't get these Nan values, while when connecting the inverter more away from the source, the Nan vlues appear.
Any idea why is this happening?
Thanks.
  2 comentarios
Franklin
Franklin el 21 de Sept. de 2023
#Itemone #Itemtwo act or effect of amending, of rectifying a fault or defect; correction.
"e. to a book"
Walter Roberson
Walter Roberson el 21 de Sept. de 2023
Sorry, I do not understand how your response will aid @Eleni Tekki in solving the problem?

Iniciar sesión para comentar.

Respuestas (1)

Sayan
Sayan el 25 de Sept. de 2023
Hi Eleni T,
I understand from your issue that you are using a "PV Array" block as a source to run the inverter in your model to feed power to your grid with the 3 feeders. However, the inverter output is 'Nan'.
The possible reasons for the issue and their fixes are mentioned below:.
  • The PV Array block (available at Simscape / Electrical / Specialized Power Systems / Sources) has an internal algebraic loop that is not solvable for the sample time defined in the model to solve the ineternal non-linear diode characteristics of the block.
  • The "Break algebraic loop in internal model" option in the "Advanced" tab of the PV Array block needs to be selected to break the algebraic loop.
If the above-mentioned solution does not work, you can follow these alternative steps to fix the issue.
  • Verify that there is no division by zero operation in your model.
  • Try changing the solver type and step size in your model.
For better understanding, you can refer the following MATLAB Answers post. A similar issue regarding the PV Array block is addressed in this post:https://www.mathworks.com/matlabcentral/answers/466337
You can further find more information on the "Break algebraic loop in internal model" section of the PV Array block in the following MATLAB documentation
Hope this helps in resolving the issue.