unbalanced load on a synchronous generator

7 visualizaciones (últimos 30 días)
K
K el 1 de Dic. de 2023
Respondida: Joel Van Sickel el 3 de En. de 2024
Hello,
I would like to apply an asymetrical load to a synchronous generator.
The original model has 3ph dynamic AC load as shown below and works perfectly fine.
I would like to apply an asymetrical load now like shown below, I applied a AC dynamic load in Y configuration, each getts a different input
I get wrong results (voltag 2.8e11V for a 400V generator)
Do you have any idea what is wrong?
Is there any possibility to apply an asymetrical load using power preferably (availabe data) and not a current load?
Thank you
reagrds,

Respuestas (1)

Joel Van Sickel
Joel Van Sickel el 3 de En. de 2024
I tested these blocks and they don't seem to work well when split into a three phase load like this (even for a balanced load). I would recomend using the variable resistor block (there are also variable capacitor and inductor blocks) to implement the asynchronous load. It will require a bit more calculations (converter desired power to desired impedance based on line voltage) but it should give you a path forward to have a controllable load that can also be unbalanced.

Categorías

Más información sobre Specialized Power Systems en Help Center y File Exchange.

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by