NI myDAQ Simulink toolbox
12 visualizaciones (últimos 30 días)
Mostrar comentarios más antiguos
Ali Zolfagharian
el 16 de Mzo. de 2017
Comentada: Jan
el 21 de Mzo. de 2017
Hi, I would like to use NI myDAQ in Simulink but I cannot find it through the Simulink toolbox. Is it any possibility for using it in Simulink. Regards.
0 comentarios
Respuesta aceptada
Archita P
el 20 de Mzo. de 2017
Firstly, make sure that the 'nidaq' legacy interface adaptor is successfully registered. In Simulink data acquisition that uses legacy interface, you can try the below mentioned workaround, if the device is not being detected inside the DAQ blocks. This issue is specific to Data Acquisition with Legacy interface in 32 bit MATLAB.
Run the MATLAB once in elevated Administrative mode in order to register the Data Acquisition Toolbox adaptor:
1. Right click on the MATLAB shortcut or the file MATLAB.exe and select "Run as Administrator". 2. Once MATLAB starts execute the "daqregister" command as normal- >> daqregister('nidaq') 3. Close MATLAB and start it as usual.
After adaptor registration with daqregister('nidaq') as described in the solution above , verify that the device is accessible with the legacy interface: >> hw = daqhwinfo('nidaq') >> hw.InstalledBoardIds >> hw.BoardNames >> hw.ObjectConstructorName
3 comentarios
Jan
el 21 de Mzo. de 2017
[Moved from flag (Note: Flags are thought to point to inappropriate contents)]
Ali Zolfagharian wrote:
That is a comprehensive and very essential answer to apply myDAQ in Simulink
Más respuestas (1)
Walter Roberson
el 20 de Mzo. de 2017
You need to install Data Acquisition Toolbox Support Package for National Instruments NI-DAQmx Devices.
Ver también
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!